Experiment of Flow Regime Map and Local Condensing Heat Transfer Coefficients Inside Three Dimensional Inner Microfin Tubes

在线阅读 下载PDF 导出详情
摘要 Thispaperdevelopedanewtypeofthreedimensionalinnermicrofintube,Theexperimentalresultsoftheflowpatternsforthehorizontalcondensationinsidethesetubesarereportedinthepaper,Theflowpatternsforthehirizontalcondensationinsidethenewmadetubesaredividedintoannularflowstratifiedflowandintermittentflowwithinthetestconditions.Theexperimentsofthelocalheattransfercoefficientsforthedifferentflowpatternshavebeensystematicallycariedout,Theexperimentsofthelocalheattransfercoefficientschangingwiththevapordrynessfractionhavealsobeencarriedout.Ascomparedwiththeheattransfercoefficientsofthetwodimensionalinnermicrofintubes,thoseofthethreedimensionalinnermicrofintubesincrease47-127%fortheannularflowregion,38-183%forthestratifiedflowand15-75%,fortheintermittentflow,respectively.Theenhancementfactorofthelocalheattransfercoefficientsisfrom1\8-6\9forthevapordrynessfractionfrom0.05to1.
机构地区 不详
出版日期 1999年01月11日(中国期刊网平台首次上网日期,不代表论文的发表时间)