简介:摘要:随着特高压建设不断推向深入,以往工程项目管理模式已经不能完全适应工程的发展,项目管理模式也应与时俱进,不断摸索和创新。在工程建设的不同阶段,现场工序管理的工作重点也不尽相同,笔者结合工作角度出发,对各施工工序之间的衔接对现场进度管理的影响进行了分析,结合实践提出了改进的方法。 关键词:工序衔接 进度管理 项目管理 Abstract: With the development of EHV project construction, conservative PM model has no longer suited new development of EHV project, new PM models should be derived, and innovation of management should be explored as well. The key emphasis of working procedure varies through different stages of project, based on the practice of progress control, the effects of convergence among different constructing processes upon schedule management is analyzed and improvement of management measures based on practice have been demonstrated. Key word: convergence of working procedure,progress control,PM
简介:摘要:电力电缆线路是城市电网中重要的组成部分,其安全可靠稳定运行对于城市电网具有重要意义。为掌握运行多年的交联聚乙烯 (XLPE)电缆绝缘劣化状况及出现劣化的原因,采用热重法、红外光谱、机械强度试验分析了退运的 14条 110 kV和 220 kV XLPE电缆绝缘。研究了电缆绝缘材料的热稳定性、物质成分及机械性能与电缆绝缘劣化的对应关系,并分析了 14条退运电缆历史运行数据。结果表明, 14条退运电缆中,有 4条电缆绝缘出现了劣化,而这些电缆都经受过穿越故障电流或外部高温;起始分解温度、羰基指数、断裂能对表征 XLPE电缆绝缘的劣化状况有很好的一致性,当绝缘出现劣化时,其起始分解温度降低、羰基指数升高、断裂能减小:交联电缆经受大的故障电流冲击或外部高温,都会加快绝缘的劣化。
简介: 摘要:随着电力 事业 的发展,我国的 高压 电气试验工作也取得了很大的发展和进步,这种情况下,为了更好的发挥电气试验的效果,避免人身伤亡和安全事故的产生,就应该对 试验中 存在的危险点进行严格的预防和控制,也就是说应该做好应对措施。基于此,本文对高压电气试验中的安全重要性 、 危险点及 防护 措施进行分析和探讨。 关键词:高压电气试验;危险点; 防护 措施 1 高压电气试验的类型和特点 高压电气试验主要是对电气设备的绝缘性能进行试验 , 若 被试电气设备施加高压 后 (工频高压或冲击高压),在规定电压下不发生击穿、闪络或其他异常 现象 时,则视为 绝缘 合格。高压电气试验按试验方法一般可分为无破坏性检查试验、耐压试验、在线监测和研究性试验等几类 , 对电气设备进行运行维护所采取的试验方法一般指前两种。无破坏性试验是在电压较低情况下进行的试验,一般不会对绝缘造成破坏,其测试项目包括测量绝缘电阻、泄漏电流、介质损耗因数及吸收比试验等。无破坏性试验不能充分判断绝缘的耐压强度,所以仍需要进行耐压试验,以模拟电气设备在实际运行中的状况。耐压试验可以更有效地发现潜在危险和集中性缺陷,但会对绝缘造成损伤甚至发生击穿,其试验内容包括直流耐压试验、交流耐压试验和冲击耐压试验等。 2 高压电气试验安全重要性分析 做好高压电气试验的安全工作十分重要,主要表现在以下三个方面: 2.1 有利于电气设备检修工作的展开 为了提高电气设备性能的可靠性,需要做好电气设备检修工作,使其在运行中处于高效、稳定的工作状态,以此来保证电力系统安全稳定的运行。高压电气试验是电气设备检修过程中必不可少的一个重要环节,通过高压电气试验来合理判断电气设备的绝缘性能。由于高压电气试验属于危险性较高的 工作 ,因此 在进行 高压电气试验时要做好安全保障工作,避免由于存在安全隐患而导致设备损坏和人员伤亡事故发生,从而保证电气设备检修工作的顺利开展。